The STEGO IO-Link Actuator Hub AHC 072 can switch up to three actuators or loads on process level via relays. Switching commands for the loads are received via the IO-Link interface from a higher-level control unit: edge computer, cloud, PLC control, etc. The actuator hub supports both AC and DC loads, independent of their function or whether they have a communication interface. This means that analog devices, such as heaters or filter fans, can easily be integrated into a digital network.Number of relay outputs 1 to 3 contact makers (NO), with 3 optical indicators Max. switching capacity AC 240 V, 10 A, DC 30 V, 10 A Max. inrush current AC 16 A for 10 sec Actuator connection 2-pole Push-In terminals (3 x) IO-Link connection M12 round plug connector, IEC 61076-2-101, 4-pin, A-coded Electrical protection Reverse-polarity, short circuit, overvoltage protection Mounting clip for 35 mm DIN rail, EN 60715 and screw mounting (M5) Casing plastic according to UL94 V-0, light grey More information: | | Operating Voltage: | 24V dc | Series: | AHC 072 | Communication Protocol: | IO-LINK | Interface: | IO-Link |
|