Salicru's SLC TWIN RT2 UPS range is a highly advanced continuity solution for the electrical protection of critical systems. It combines the most reliable double-conversion technology (AC/DC-DC/AC) on the market and boasts a unity output power factor (VA=W) to enable it to power systems with high energy requirements, while offering high operating efficiency. The range of power ratings from 700 VA(W) to 3,000 VA(W), it comes in a 2U, convertible to tower format, with a swivel mount LCD display, according to the needs of the facility. Also available are solutions with an extra charger and additional battery modules for applications that require greater backup. In terms of communications, it features an RS-232/USB interface compatible with HID protocol and a smart slot that can optionally hold an SNMP card, MODBUS or potential free contacts; also available are software packages for local or virtual monitoring and management of protected devices. Other outstanding features include: 50/60 or 60/50 Hz frequency converter, emergency stop (EPO), and programmable outputs for critical/non-critical loads.
Weight & dimensions | Width | 438 mm |
| Depth | 490 mm |
| Height | 88 mm |
| Weight | 9400 g |
Battery | Battery technology | Lead-Calcium (Pb-Ca) |
| Battery recharge time | 3 h |
| Cold start | Yes |
| Charge type | I/U |
Operational conditions | Operating temperature (T-T) | 0 - 40 °C |
| Storage temperature (T-T) | 0 - 95 °C |
| Operating altitude | 0 - 5000 m |
Logistics data | Harmonized System (HS) code | 85078000 |
Design | Form factor | Rackmount/Tower |
| Product colour | Black |
| Rack capacity | 2U |
| Cooling type | Active |
| Display type | LCD |
| LED indicators | Yes |
| Safety | EN 62040-1:2008, EN 62040-2:2006(C2), EN 62040-3:2011 |
| Certification | ISO 9001 ISO 14001 |
Features | UPS topology | Double-conversion (Online) |
| Output power capacity | 2 kVA |
| Output power | 2000 W |
| Input operation voltage (min) | 200 V |
| Input operation voltage (max) | 240 V |
| Input frequency | 50/60 Hz |
| Output operation voltage (min) | 200 V |
| Output operation voltage (max) | 240 V |
| Output frequency regulation | 3 Hz |
| Output voltage regulation | 1 % |
| Efficiency | 91 % |
| Power factor | 1 |
| Emergency Power Off (EPO) | Yes |
| Overload capacity (10 minutes) | 110 % |
| Overload capacity (5 minute) | 130 % |
| Overload capacity (1 minute) | 130 % |
| Output voltage Total Harmonic Distortion (THD) | 2 % |
| Input current Total Harmonic Distortion (THD) | 5 % |
| Total Harmonic Distortion (THD) (linear load) | 2 % |
| Total Harmonic Distortion (THD) (non-linear load) | 4 % |
| Noise level | 55 dB |
| Surge protection | Yes |
| Power protection features | Under voltage |
| Input frequency converter | Yes |
| Synchronisation with mains | 3 Hz |
| Synchronisation without mains | 0.1 Hz |
| Temperature voltage compensation | Yes |
Ports & interfaces | AC outlet types | C13 coupler |
| AC outlets quantity | 8 AC outlet(s) |
| USB port | Yes |
| USB 2.0 ports quantity | 1 |
| Serial interface | Yes |
| Serial interface type | RS-232 |
| RS-232 ports | 1 |
| SmartSlot | Yes |
| Programmable sockets | Yes |
Other features | Battery type | AGM |